MTL4516C SWITCH/ PROXIMITY DETECTOR INTERFACE 2-channel

description:MTL4516/C – MTL5516C SWITCH/ PROXIMITY DETECTOR INTERFACE 2-channel, with line fault detection...
BASIC INFO
Production overviews
       
                           MTL 4500 Intrinsically Safe Isolators  MTL4516C

MTL4516/C – MTL5516C SWITCH/ PROXIMITY DETECTOR INTERFACE 2-channel, with line fault detection
The MTLx516/C enable two safe-area loads to be controlled by a switch or proximity detector located in a hazardous-area. When selected, open or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module. Phase reversal for each channel is selected by a switch on the side of the module and output is provided by changeover relay contacts.
 
                                           



MTL4516C safe isolator product specification
SPECIFICATION
See also common specification
Number of channels
Two
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are
indicated by an LED for each channel. The channel output relay is
de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Two single-pole relays with changeover contacts
Note: reactive loads must be adequately suppressed
Maximum current consumption
35mA at 24V
Power dissipation within unit
0.84W at 24V
LED indicators
Green: power indication
Yellow: two: channel status, on when output energised
Red: two: LFD indication, on when line fault detected
Safety description (each channel)
Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc

 

Other related models for MTL4500 series as below for your reference.
MTL4501-SR       
MTL4504                
MTL4510              
MTL4510B                
MTL4511
MTL4513             
MTL4514D             
MTL4514_B          
MTL4516                   
MTL4516C
MTL4517             
MTL4521                
MTL4521L            
MTL4523                  
MTL4523L
MTL4523R           
MTL4523V-VL        
MTL4524              
MTL4524S                
MTL4525  
MTL4526             
MTL4541                
MTL4541A            
MTL4541AS              
MTL4541B
MTL4541P           
MTL4541S              
MTL4541T            
MTL4544                  
MTL4544A
MTL4544AS         
MTL4544B               
MTL4544D           
MTL4544S                 
MTL4546
MTL4546C           
MTL4546S              
MTL4546Y            
MTL4549                  
MTL4549C
MTL4549Y           
MTL4573                
MTL4575              
MTL4576-RTD           
MTL4576-THC
MTL4581             
MTL4582B              
MTL4531              
MTL4532                   
MTL4561
MTL4599             
MTL4599N


For more information about MTL4516C, please feel free to contact me here.
Contact details

HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85880977
Mobile :86-13545206420(Whatapp&Wechat is available)
Fax:86-027-85309780
Skype:Diana@hkxytech.com
E-mail:Diana@hkxytech.com    Or Cc:
Dianatian118@gmail.com
Website:www.hkxy-lowvoltage.com







 
Pre:MTL4516 safe isolator 2channel DI relay output Next:MTL4517 safe isolator 2channel DI relay output + LFD alarm