BASIC INFO
Production overviews
MTL5018AC Intrinsically Safe Isolators product introduction
SPECIFICATION
Number of channels :Two
Location of switches
Zone 0, IIC, T4–6 hazardous area Div. 1, Group A hazardous location
Safe-area output: Two relays with changeover contacts
Hazardous-area inputs: Inputs conforming to NAMUR/DIN 19234 standards for proximity detectors
Voltage applied to sensor :7 to 9V from 1kΩ ±10%
Input/output characteristics:Normal (reverse) phase: output energised (de-energised) if Iin >2.1mA or Rin 10kΩ Hysteresis: 200μA, typica
Line fault detection (LFD)
User-selectable via switches on the top of the unit. Line faults are indicated by an LED for each channel. A detected line fault de-energises the relay.
Open-circuit alarm on if Iin 250μA
Short-circuit alarm on if Rin 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch
Phase reversal: Independent for each channel, user-selectable
Relay type :Single pole, changeover contacts
Note: reactive loads must be adequately suppressed
Relay characteristics
Response time:
10ms maximum
Contact rating:
250V ac, 2A, cosø >0.7 40V dc, 2A, resistive load
LED indicators
Green: power indication
Yellow: two: status of each channel (on when outputs are energised)
Red: two: LFD indication for each channel (on when line fault detected)
Maximum power dissipation:<2.5W
Isolation 250V ac or dc between power supply, hazardous-area circuits and relay outputs
Safety description (each channel)
10.5V, 800Ω, 14mA, Um= 250V rms or dc
Power Supply :
85 to 265V ac 45 to 65 Hz
Other relevant models for MTL5500 Safe Isolators
MTL5018AC MTL5501-SR MTL5510 MTL5510B MTL5511
MTL5513 MTL5514 MTL5514D MTL5516C MTL5517
MTL5521 MTL5522 MTL5523 MTL5523V - VL MTL5524
MTL5524 MTL5526 MTL5541 MTL5541A MTL5541AS
MTL5541S MTL5544 MTL5544A MTL5544AS MTL5544D
MTL5544S MTL5546 MTL5546Y MTL5549 MTL5549Y
MTL5573 MTL5575 MTL5576-RTD MTL5576-THC MTL5581
MTL5582 MTL5582B MTL5991 MTL5531 MTL5532
MTL5533 MTL5561 MPA5500 MTL5051 MTL505
MTL5314 MTL5599
For more information about MTL5018AC, please feel free to contact me here.
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85880977
Mobile :86-13545206420(Whatapp&Wechat is available)
Fax:86-027-85309780
Skype:Diana@hkxytech.com
E-mail:Diana@hkxytech.com Or Cc:Dianatian118@gmail.com
Website:www.hkxy-lowvoltage.com
MTL 5500 Intrinsically Safe Isolators MTL5018AC safety barrier
MTL5018AC SWITCH/ PROXIMITY DETECTOR INTERFACE two-channel, with line fault detection and phase reversal
The MTL5018ac enables two safe-area loads to be controlled by two switches or proximity detectors located in a hazardous area. Two relay outputs are provided. Independent phase reversal control allows an alarm condition to be signalled for either state of the sensor. A selectable line fault detect (LFD) facility detects an open or short circuit in either field circuit.
MTL5018AC SWITCH/ PROXIMITY DETECTOR INTERFACE two-channel, with line fault detection and phase reversal
The MTL5018ac enables two safe-area loads to be controlled by two switches or proximity detectors located in a hazardous area. Two relay outputs are provided. Independent phase reversal control allows an alarm condition to be signalled for either state of the sensor. A selectable line fault detect (LFD) facility detects an open or short circuit in either field circuit.
MTL5018AC Intrinsically Safe Isolators product introduction
SPECIFICATION
Number of channels :Two
Location of switches
Zone 0, IIC, T4–6 hazardous area Div. 1, Group A hazardous location
Safe-area output: Two relays with changeover contacts
Hazardous-area inputs: Inputs conforming to NAMUR/DIN 19234 standards for proximity detectors
Voltage applied to sensor :7 to 9V from 1kΩ ±10%
Input/output characteristics:Normal (reverse) phase: output energised (de-energised) if Iin >2.1mA or Rin 10kΩ Hysteresis: 200μA, typica
Line fault detection (LFD)
User-selectable via switches on the top of the unit. Line faults are indicated by an LED for each channel. A detected line fault de-energises the relay.
Open-circuit alarm on if Iin 250μA
Short-circuit alarm on if Rin 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch
Phase reversal: Independent for each channel, user-selectable
Relay type :Single pole, changeover contacts
Note: reactive loads must be adequately suppressed
Relay characteristics
Response time:
10ms maximum
Contact rating:
250V ac, 2A, cosø >0.7 40V dc, 2A, resistive load
LED indicators
Green: power indication
Yellow: two: status of each channel (on when outputs are energised)
Red: two: LFD indication for each channel (on when line fault detected)
Maximum power dissipation:<2.5W
Isolation 250V ac or dc between power supply, hazardous-area circuits and relay outputs
Safety description (each channel)
10.5V, 800Ω, 14mA, Um= 250V rms or dc
Power Supply :
85 to 265V ac 45 to 65 Hz
Other relevant models for MTL5500 Safe Isolators
MTL5018AC MTL5501-SR MTL5510 MTL5510B MTL5511
MTL5513 MTL5514 MTL5514D MTL5516C MTL5517
MTL5521 MTL5522 MTL5523 MTL5523V - VL MTL5524
MTL5524 MTL5526 MTL5541 MTL5541A MTL5541AS
MTL5544S MTL5546 MTL5546Y MTL5549 MTL5549Y
MTL5573 MTL5575 MTL5576-RTD MTL5576-THC MTL5581
MTL5582 MTL5582B MTL5991 MTL5531 MTL5532
MTL5533 MTL5561 MPA5500 MTL5051 MTL505
MTL5314 MTL5599
For more information about MTL5018AC, please feel free to contact me here.
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85880977
Mobile :86-13545206420(Whatapp&Wechat is available)
Fax:86-027-85309780
Skype:Diana@hkxytech.com
E-mail:Diana@hkxytech.com Or Cc:Dianatian118@gmail.com
Website:www.hkxy-lowvoltage.com