low voltage

Hotline

Schneider ATS22C21Q soft starter-ATS22-control 220V-power 230V(55kW)/400...440V(110kW)

description:Soft starters Altistart 22 series from 4-400 kw ATS22C21Q...
BASIC INFO
Product overview



                               Schneider soft starter-ATS22-control 220V-power 230V(55kW)/400...440V(110kW)



                                                            Altistart22
Schneider soft starter-ATS22-control 220V-power 230V(55kW)/400...440V(110kW) ATS22C21Q

ATS22C21Q product specification as below.

  • Characteristics

    Main
    range of product
    Altistart 22
     
    product or component type
    Soft starter
     
    product destination
    Asynchronous motors
     
    product specific application
    Pumps and fans
     
    component name
    ATS22
     
    network number of phases
    3 phases
     
    [Us] rated supply voltage
    230...440 V - 15...10 %
     
    motor power kW
    110 kW 400 V
    110 kW 440 V
    55 kW 230 V
     
    factory setting current
    195 A
     
    power dissipation in W
    117 W for standard applications
     
    utilisation category
    AC-53A
     
    type of start
    Start with torque control (current limited to 3.5 In)
     
    IcL starter rating
    210 A connection in the motor supply line for standard applications
     
    IP degree of protection
    IP00
     
    Complementary
    assembly style
    With heat sink
     
    function available
    Internal bypass
     
    supply voltage limits
    195...484 V
     
    supply frequency
    50...60 Hz - 10...10 %
     
    network frequency
    45...66 Hz
     
    device connection
    In the motor supply line
    To the motor delta terminals
     
    [Uc] control circuit voltage
    230 V -15...10 % 50/60 Hz
     
    control circuit consumption
    20 W
     
    discrete output number
    2
     
    discrete output type
    Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
    Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
     
    minimum switching current
    100 mA 12 V DC relay outputs
     
    maximum switching current
    5 A 250 V AC resistive 1 relay outputs
    5 A 30 V DC resistive 1 relay outputs
    2 A 250 V AC inductive 0.4 20 ms relay outputs
    2 A 30 V DC inductive 7 ms relay outputs
     
    discrete input number
    3
     
    discrete input type
    Logic LI1, LI2, LI3 5 mA 4.3 kOhm
     
    discrete input voltage
    24 V <= 30 V
     
    discrete input logic
    Positive logic LI1, LI2, LI3 < 5 V and <= 2 mA > 11 V >= 5 mA
     
    output current
    0.4...1 Icl adjustable
     
    PTC probe input
    750 Ohm
     
    communication port protocol
    Modbus
     
    connector type
    1 RJ45
     
    communication data link
    Serial
     
    physical interface
    RS485 multidrop
     
    transmission rate
    4800, 9600 or 19200 bps
     
    installed device
    31
     
    protection type
    Phase failure line
    Thermal protection starter
    Thermal protection motor
     
    marking
    CE
     
    type of cooling
    Forced convection
     
    operating position
    Vertical +/- 10 degree
     
    height
    425 mm
     
    width
    206 mm
     
    depth
    299 mm
     
    product weight
    33 kg
     
    power range
    55...100 kW at 200...240 V 3 phases
    110...220 kW at 380...440 V 3 phases
     
    motor starter type
    Soft starter
     
    Environment
    electromagnetic compatibility
    Conducted and radiated emissions level A IEC 60947-4-2
    Damped oscillating waves level 3 IEC 61000-4-12
    Electrostatic discharge level 3 IEC 61000-4-2
    Immunity to electrical transients level 4 IEC 61000-4-4
    Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3
    Voltage/current impulse level 3 IEC 61000-4-5
     
    standards
    EN/IEC 60947-4-2
     
    product certifications
    C-Tick
    CSA
    CCC
    GOST
    UL
     
    vibration resistance
    1.5 mm 2...13 Hz EN/IEC 60068-2-6
    1 gn 13...200 Hz EN/IEC 60068-2-6
     
    shock resistance
    15 gn 11 ms EN/IEC 60068-2-27
     
    noise level
    56 dB
     
    pollution degree
    Level 2 IEC 60664-1
     
    relative humidity
    0...95 % without condensation or dripping water EN/IEC 60068-2-3
     
    ambient air temperature for operation
    -10...40 °C without derating
    > 40...< 60 °C with current derating 2.2 % per °C
     
    ambient air temperature for storage
    -25...70 °C
     
    operating altitude
    <= 1000 m without derating
    > 1000...< 2000 m with current derating of 2.2 % per additional 100 m
     
    Offer Sustainability
    Sustainable offer status
    Green Premium product
     
    RoHS (date code: YYWW)
    Compliant  - since  0939  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
     
    REACh  
    Product environmental profile  
    Product end of life instructions  
    Contractual warranty
    Warranty period
    18 months
     
  • Other selection models for Schneider Altistart 22 for your reference.
  • ATS22C21Q
    ATS22C25Q
    ATS22C48Q
    ATS22D62Q
    ATS22C17Q
    ATS22D17Q
    ATS22D32Q
    ATS22D88Q
    ATS22C14Q
    ATS22C32Q
    ATS22C41Q
    ATS22C59Q
    ATS22D47Q
    ATS22D75Q
    ATS22C11Q

For more details about Schneider Altistart22,please feel free to contact me, thanks.

Contact details

HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85880977
Mobile :86-13545206420(Whatapp&Wechat is available)
Fax:86-027-85309780
Skype:Diana@hkxytech.com
E-mail:Diana@hkxytech.com
Website:http://www.hkxy-lowvoltage.com/
 
           
Pre:None Next:ATS22C48Q 100% original soft starter with good price