Danfoss 080G0112 MCX06D controller for refrigeration automation and I/O planning
Danfoss 080G0112 is the MCX06D programmable controller in a single-pack version with LCD, RS485 and real-time clock. Danfoss lists six digital relay outputs, a 24 V supply and CANBUS, RS485 and MODBUS communications. The shared category collage is not an exact 080G0112 unit image.
Key technical data
| Technical item | Verified value / selection note |
|---|---|
| Complete order number | 080G0112 |
| Manufacturer designation | MCX06D programmable controller, six relays |
| Supply voltage | 24 V AC/DC in product record |
| Digital I/O | 8 digital inputs and 6 digital outputs |
| Analog I/O | 4 analog inputs and 3 analog outputs |
| Communications | CANBUS, RS485 and MODBUS listed by Danfoss |
| Local display | LCD; real-time clock listed for this reference |
| Mounting / enclosure | DIN rail / IP40 in Danfoss product specification |
The Danfoss 080G0112 details above describe the exact reference; final selection must also match the printed label and the installed equipment. The shared product image is only a category reference.
Confirm the installed program
The hardware reference 080G0112 alone does not describe the application software running on a refrigeration system. Before replacing an MCX06D, identify the machine program, parameter backup, connected I/O and communication addresses. Keep the existing 080G0112 firmware or project record with the equipment file.
I/O and field wiring
Danfoss publishes eight digital inputs, six digital outputs, four analog inputs and three analog outputs for 080G0112. Map each connected sensor, actuator and alarm circuit before wiring a replacement. Check voltage type and terminal allocation against the equipment drawing rather than assuming identical use of every available channel.
Network and display fit
080G0112 includes an LCD and manufacturer-listed CANBUS, RS485 and MODBUS communication capabilities. Confirm which port and protocol the actual installation uses, then verify addressing, termination and connected supervisory equipment. A similar 080G reference may omit a display, use another packaging configuration or have different I/O.
Commissioning after replacement
Check that the 24 V supply, connector kit, DIN-rail mounting and cabinet environment match Danfoss 080G0112. A qualified technician should load the approved program and test control sequences, alarms and fail-safe behavior before returning the refrigeration plant to service.
Similar-looking Danfoss order references
The 080G entries below are search references across Danfoss electronic controls. They may be different controllers, displays or accessories, so their codes must be verified separately from 080G0112.
Final order and receiving review
For Danfoss 080G0112, provide the full printed model, application duty, electrical or process interface, and current site documentation when requesting a quote. Do not approve a similar-looking number as a drop-in replacement without checking its own manufacturer data.
On receipt, inspect the Danfoss 080G0112 label and physical interfaces against the agreed order. Record condition, supplied accessories and the commissioning result so later maintenance enquiries can use the complete identity.