low voltage

Hotline

Industrial Buyer Technical Review for Hirschmann OZD Profi 12M G12 EEC PRO: Verified Hirschmann Profibus Electrical-To-Optical Repeater

description:Hirschmann OZD Profi 12M G12 EEC PRO: model OZD Profi 12M G12 EEC PRO, part 943907321. Review verified manufacturer data, interfaces, installation conditions and exact supply scope....
BASIC INFO

What to Confirm Before Ordering Hirschmann OZD Profi 12M G12 EEC PRO for an Industrial Network Project

Confirm the full ordering identity

Hirschmann OZD Profi 12M G12 EEC PRO identifies the Hirschmann PROFIBUS electrical-to-optical repeater, model OZD Profi 12M G12 EEC PRO, part number 943907321. Keep the complete model and part number together in the RFQ because nearby family members may differ in interfaces, optical medium, environmental range, software, housing or supply arrangement.

Match the repeater topology

The exact interface statement is 2 x optical: 4 sockets BFOC 2.5 (STR); 1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1. Count the required electrical PROFIBUS segments and optical channels, then choose a line, star or redundant arrangement supported by the project design. G11, G12, G22, P11, P12 and P22 suffixes are not interchangeable shorthand; they describe different connection resources.

Calculate the optical link

This model should be reviewed for 860 nm multimode fiber planning. Confirm fiber construction, wavelength, attenuation, connector type, splice loss and route length at both ends. Use the published link budget with an engineering reserve rather than treating the maximum catalog distance as a guaranteed result for every installed cable.

Check environment and mounting

The source lists 18 ... 32 VDC, typ. 24 VDC, -20 to +60 °C °C, and dimensions of 35 x 156 x 119 mm. Confirm whether the requested version is standard, EEC or PRO and compare its protection and mounting details. Cabinet temperature, power redundancy, grounding, clearance and hazardous-area documentation require project-specific review.

Ordering and engineering reference

BrandHirschmann
Exact modelOZD Profi 12M G12 EEC PRO
Part number943907321
Product functionInterface converter electrical/optical for PROFIBUS-field bus networks; repeater function; for plastic FO; short-haul version
Ports / interfaces2 x optical: 4 sockets BFOC 2.5 (STR); 1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1
Signal typePROFIBUS (DP-V0, DP-V1, DP-V2 und FMS)
Operating voltage18 ... 32 VDC, typ. 24 VDC
Power reference4.8 W
Operating temperature-20 to +60 °C °C
Dimensions35 x 156 x 119 mm
MountingDIN rail
ProtectionIP20
Multimode fiber (MM) 50/125 µm3000 m, 13 dB link budget at 860 nm; A = 3 dB/km
Multimode fiber HCS (MM) 200/230 µm1000 m 18 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve

Hirschmann industrial networking product reference photograph

Reference photograph: shared Hirschmann product image. The photographed unit may be a different model or product type; this image does not establish the configuration or availability of Hirschmann OZD Profi 12M G12 EEC PRO.

Preserve PROFIBUS commissioning data

Record baud rate, segment length, termination position, node layout and optical status results during commissioning. Keep label photographs and the accepted fiber schedule with the device record. These details help maintenance teams distinguish a fiber fault, electrical-bus issue or configuration problem when service is later required.

Request the exact OZD version

Quote Hirschmann OZD Profi 12M G12 EEC PRO with part number 943907321, quantity, destination and required delivery date. Include the existing or proposed topology, fiber type, route length and environmental conditions. Ask the supplier to identify included terminal blocks and any separately ordered fiber connectors, power equipment or mounting accessories.

Replacement decision note

Port count or appearance alone does not establish replacement compatibility. Compare exact identity, interfaces, supply, mechanics, environmental limits and approvals together. Where an installed unit is involved, capture its settings and wiring before removal and document the reason for replacement.

Technical reference: manufacturer source for OZD Profi 12M G12 EEC PRO. Verify current documentation and the delivered revision before final engineering approval.

 

 

 

Pre:Hirschmann OZD Profi 12M G12 EEC Profibus Electrical-To-Optical Repeater | Configuration and RFQ Guide for Industrial Network Projects Next:How to Specify Hirschmann OZD Profi 12M G12 PRO | Profibus Electrical-To-Optical Repeater, Interfaces and Supply Scope